FireShield
Conventional Fire Alarm Panels
The
FireShield fire alarm family is the ideal solution for both new
and retrofit installations. It consists of three, five and 10 zone
conventional fire alarm control panels, an integrated DACT/Dialer,
serial annunciator modules, and serial remote relay modules - all
of which are microprocessor-controlled for trouble-free operation.
FireShield
panels incorporate features like front panel programming, one person
walk testing, and selectable IDC and NAC types. These features are
designed to simplify installation, operation and maintenance while
keeping costs in-check.
FireShield
panels are powerful enough to meet the demands of todays installations
while leaving plenty of room to grow in the future. All available
current may be used for notification appliances, or up to 0.5 amps
can be used as auxiliary current.
FireShield
provides smoke and fire detection, occupant notification and off-premises
signaling for small- to medium sized buildings. Each IDC can be
configured for either Class B or Class A operation and one of eight
operating modes.
NACs
may also be configured for either Class B or Class A operation.
Additionally, NACs can be individually configured for one of three
outputs. These are Genesis, Continuous or Temporal. The Genesis
selection allows independent horn control over two wires and provides
precision synchronization for Genesis devices, all without the need
for a Genesis Signal Master accessory.
When
configured for Genesis™ notification
appliances, FireShields Alarm Silence function will silence
connected Genesis audible appliances but Genesis strobes will remain
active until the panel is reset. When Genesis Mode is selected,
both the horns and strobes on Genesis and Enhanced Integrity notification
appliances will be synchronized across all NACs.
Control
of the panels operation is both simple and intuitive. While
the LEDs and LCD are visible with the panel door closed, the door
and bezel block access to the controls.
With
the DACT/Dialer installed, the dialers LCD display provides
two lines x 16 characters of text. For programming, the top line
displays the programming step and the lower line displays the selected
option. When not in the programming mode, the panel status is displayed.
The panels LEDs provide additional indication of panel status.